Automatic Voltage Control Units Model- AX-02 | Features and Technical Specifications : |
| |
| Input Power |
|
| |
Voltage |
: 240V ac rms + 10% |
| |
Frequency |
: 50/60 HZ |
| Output Power |
|
| |
Voltage |
: 95V dc at 240V a.c. input |
| |
Current |
: 6 Amps dc, 8 Amps for 10 secs for motor starting. |
| Field Resistance |
: 10 ohms, minimum |
| Build up |
: Less than 5V a.c. rms at AVR power input terminals. |
| Regulation |
: +/- 1% of set voltage |
| Voltage Adjustment |
: +/- 10% over 415V |
| Stability Adjustment |
: Adjustable to get stable operation and desired response. |
| Voltage Sensing |
: |
415V a.c. two line sensing. AVR senses average of the generator wave form. |
| Response time |
: Less than75 milli seconds. |
| Under frequency Protection (FRO) |
: Adjustable from 40HZ to 60HZ. |
| Parallel Operation Facility (QDC |
: |
Adjustable droop up to 6%. 5A. CT Signal from "W" phase to be connected to terminals Q1 & Q2. |
| Circuit Protection |
: |
Protection against voltage transients by L-C networks and high energy suppressors. |
| RFI Suppression |
: |
AVR includes RFI filters to filter out the RFI generated, due to power device turn on. |
| Temperature drift |
: |
Typically 0.025% per degree celcius over operating temperature range. |
| Fuse |
: 4 Amps fuse provided inside the AVR box. |
| Operating temperature |
: 20 degree celcius to +60 degree celcius ambient. |
| Power dessipation |
: 10 Watts (max). |
| Size (LBH) |
: AX02 : 140x145x45 |
| Weight |
: AX02 : 700 gms |
|