Electrical Voltage Control Unit Code-AVR-AX-04 GENERAL DESCRIPTION
- The Voltage Control Unit(AVR) is a solid state, encapsulated, state of the art design with latest technology.
- The AVR is supplying power to the exciter field of A.C. generator and will maintain gererator voltage within close limits from no load to full load, with a frequency change of not more than +- 4%.
- Upon application or rejection of rated load, the generator voltage recovers to nominal value within 0.5 sec. However, the transient performance is mainly dependent upon the exciter & a.c. generator design aspects.
- Under some circumstances the a.c. generator wave shape changes considerably from no-load to rated load due to the typw of load, hence the r.m.s average or the peak voltage does not stay in proportion. For more than 10% harmonic distortion, the voltage regulation may be outside the limit specified.
- Unbalanced load on 3 phase a.c. generators also produces regulation figures outside the limit.
- AVR has been tested at factory and set to standard voltage, frequency and stability prior t the despatch.
- AVR has been incorporated with special filters to perform satisfactorily or no linear loads.
FEATURES AND TECHNICAL SPECIFICATIONS:
Input Power
- Voltage: 240V ac rms +- 10%
- Frequency:50/60 HZ
Output Power
- Voltage: 95 V dc at 240 V a.c. input
- Current : 6 Amps dc / 8 Amps for 10 secs for motor starting
| On/off Switch with illumination. |
| Fuse Protection. |
| V-Trim pot to adjust terminal voltage. |
| QDC-Pot to adjust KVAr sharing during parallel operation. |
| Single / Parallel run switch. |
| Technical Specifications : |
| |
| Input |
: |
415V, 3 phase or 110V, 3 phase for sensing 240V, 1 Phase or 110V, 1 ph for power. |
| Output |
: 200V dc or 95V dc at 10A, 15A or 20 Adc. |
| Build up |
: 5V ac rms at VCU power input terminals. |
| Regulation |
: Within +/- 2.5% of set voltage. |
| Stability Adjustment |
: |
Adjustable to get stable operation and desired response; potentiometer in PCB |
| Under Frequency Protection (FRO) |
: Adjustable Potentiometer Provided in PCB. |
| Parallel Operation (QDC) |
: |
Adjustable droop pot, 5 amps CT Singal to be given from W Phase. |
| Circuit Protection |
: |
Protection against Voltage transients by L-C Network and high energy suppressors. |
| RFI Suppression |
: |
Filters included to filter out the RFI generated due to power device turn-on. |
| Fuse |
: Fuse protection provided. |
| Operating temperature |
: -20 degree celcius to +60 degree celcius. |
| Weight |
: 5.5 Kg |
|